uninterupted power supply

UPS5000-A Series (30 kVA to 600 kVA) UPS

The UPS5000-A series is designed as a critical power supply for medium- and large-sized data centers, scheduling centers, control centers, and management centers. As an online double conversion Uninterruptable Power Supply (UPS), it offers the highest level of protection, completely detaching the equipment from raw power, converting power from AC to DC then to AC again. As such, it provides uninterruptible AC supply with a rated voltage of 380 V/400 V/415 V, covering power supply requirements from 30 kVA to 600 kVA.

With zero transfer time to the battery, UPS5000-A offers full digital control — making it possible to keep critical loads online in case of failure — plus Insulated-Gate Bipolar Transistor (IGBT) rectification technology, which offers high voltage operation with low input losses. UPS5000-A has also passed more than 1400 tests to ensure output quality under any working conditions.

Commonly used in telecom, finance, government, transportation, and petrochemical sectors, UPS5000-A series features high reliability, up to 96% efficiency, and power density.

SPECIFICATION

Brand

Huawei

Model

UPS5000-A-30K/40K

UPS5000-A-60K/80K/120K

UPS5000-A-400K/500K/600K

Rated Capacity

30 kVA/30 kW
40 kVA/40 kW

60 kVA/54 kW
80 kVA/80 kW
120 kVA/108 kW

400 kVA/400 kW
500 kVA/500 kW
600 kVA/600 kW

Input and Output Systems

Three-phase, four wire

Rated Voltage

380 V/400 V/415 V AC

Battery Voltage

360 V to 528 V DC (30 to 44 batteries based on battery capacity: 30/40/80 kVA = 32 batteries by default; 60/120 kVA = 40 batteries by default)

Overload Capacity

30/40/80 kVA: 110% load for 60 minute; 125% load for 10 minutes; 150% load for 1 minute
60/120 kVA: 110% load for 60 minutes; 125% load for 10 minutes; 150% load for 0.5 minutes
400k/500k/600k: 110% load for 60 minute; 125% load for 10 minutes; 150% load for 1 minute

Efficiency

95.70%

96%

Noise

≤ 58 dB

≤ 64 dB

≤ 70 dB

Communications

Dry contacts, RS485, and SNMP

Dimensions (H x W x D)

500 mm x 264 mm x 800 mm

1020 mm x 440 mm x 850 mm

2000 mm x 1200 mm x 850 mm (400k/500kVA)
2000 mm x 2000 mm x 850 mm (600 kVA)